EasyManua.ls Logo

Avery Weigh-Tronix XR Series - Page 23

Avery Weigh-Tronix XR Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XR Series Installation and Technical Instructions 23
20 mA Current Loop Wiring
1. Set the Communication Input Jumper (JP 1) to LOOP.
2. Terminate the indicator’s communication wires at the 20 mA Current
Loop terminal (J5), shown in Figure 3.5.
Figure 3.5 20mA Current Loop Terminal
See table below for pin assignments:
20 mA Current Loop Mode Switch
After the current loop is wired, ACTIVE or PASSIVE mode must be
selected (SW 10) on the controller board.
Select Active mode if the XR is required to supply the current to the
communicating device.
Select Passive mode if the communicating device (indicator) supplies
the current to the XR.
If unsure of these requirements, check the device’s manual.
Figure 3.6 20 mA Mode Switch
INDICATOR TO XR
20 mA TX + RECEIVE POSITIVE (RX +)
20 mA TX - RECEIVE NEGATIVE (RX -)

Other manuals for Avery Weigh-Tronix XR Series

Related product manuals