Figure 7 Status LED and SDC Admin button
3. While still pressing the ADMINbutton, reconnect the power, and continue to hold the button for another
15 seconds until the status LED turns yellow , then release.
4.
Wait 15 minutes or until the status LED turns blue before provisioning. See Provisioning on page15.
Legacy wiring
Sometimes legacy wiring (unshielded and straight through, rather than shielded twisted pair, often 22-6)
results in slower connections and dropped packets between the Avigilon reader and SDC. To remedy this, you
can switch GND and VIN with +B and -A connections on the SDC and readers to ensure the data pair (+B and -
A) are using the alternate pair of legacy wires.
Troubleshooting 23