33
Chapter 5. Communication Data
Data type Data name Address Access Description Note
Decimal
(W)
Hex
(H)
Read Write
AUR tag* AUR tag 7000
7016
1B58
1B68
0000H to FFFFH 34 characters in ASCII code
(17 characters in 2-byte code)
can be stored.
AUR Memo* AUR Memo 7017
7059
1B69
1B93
0000H to FFFFH 86 characters in ASCII code
(43 characters in 2-byte code)
can be stored
Event (read
only)*
Condition for event 7060 1B94 x 0035H (fixed)
7061 1B95 x Bit 0: UV flame detector check
(combustion time).
0: not set
1: set
Bit 1: product service life check (total
operating time).
0: not set
1: set
Bit 2: product service life check (total
combustion count).
0: not set
1: set
Bit 3: false flame
0: not set
1: set
Bit 4: flame relay OFF
0: not set
1: set
Bit 5: flame relay OFF (shutter closed)
0: not set
1: set
Bits 6 to 15
Undefined
Reads set events with bits.
UV flame detector check (combustion
time)
7069 1B9D x 0036H
7070 1B9E x 0 to 25000 (0 to 61A8H) hours
Product service life check (total
operating time)
7071 1B9F x 0037H
7072 1BA0 x 0 to 65000 (0 to FDE8H) hours
Product service life check (total
combustion count)
7073 1BA1 x 0038H
7074 1BA2 x 0 to 10 (0 to AH) times
Event relay output condition setting 7075 1BA3 x 405AH: event output
403CH: synchronized with start check
relay
Event (write
only)
Condition for event 7100 1BBC Bit 0: UV flame detector check
(combustion time).
0: not set
1: set
Bit 1: product service life check (total
operating time).
0: not set
1: set
Bit 2: product service life check (total
combustion count).
0: not set
1: set
Bit 3: false flame
0: not set
1: set
Bit 4: flame relay OFF
0: not set
1: set
Bit 5: flame relay OFF (shutter closed)
0: not set
1: set
Bits 6 to 15
Undefined
Writing 2-word event
settings (p.38)
The count returns to 0 when
the power is turned on
or after data is written to
EEPROM.
7101 1BBD 0035H