34
Chapter 5. Communication Data
Data type Data name Address Access Description Note
Decimal
(W)
Hex
(H)
Read Write
Event (write
only)
UV flame detector check (combustion
time)
7109 1BC5 0 to 61A8H (0 to 25000 hours)
Writing 2-word event
settings (p.38)
The count returns to 0 when
the power is turned on
or after data is written to
EEPROM.
7110 1BC6 0036H
Product service life check (total
operating time)
7111 1BC7 0 to FDE8H (0 to 65000 hours)
7112 1BC8 0037H
Product service life check (total
combustion count)
7113 1BC9 0 to AH (0 to 10 times) The value calculated by
multiplying the data range by
10000 is used to determine
whether an event has
occurred.
Writing 2-word event
settings (p.38)
The count returns to 0 when
the power is turned on
or after data is written to
EEPROM.
7114 1BCA 0038H
Event relay output condition setting 7115 1BC8 405AH: event output
403CH: synchronized with start check
relay
The event output is set up
before the product is shipped.
The count returns to 0 when
the power is turned on
or after data is written to
EEPROM.
EEPROM
write
request
Write AUR settings to EEPROM request 7200 1C20 5AH: request to write data to EEPROM
3CH: writing to EEPROM complete
Writes values from addresses
7100 to 7115 to EEPROM.
After changing a value, be
sure to write it to EEPROM.
After you write values to
EEPROM, the values at
addresses 7100 to 7115
change to 0.
Flame
logger
Flame logger processing status 8000 x 5AH: processing in progress
Other than 5AH: normal
Recorded data 0.1 s after trigger 8100 x Bit 0: undefined
Bit 1: startup input
0: no start input
1: start input
Bits 2 to 3
Undefined
Bit 4: flame input
0: no flame input
1: flame input
Bit 5
Undefined
Bit 6: start check relay
0: OFF
1: ON
Bit 7: flame relay
0: OFF
1: ON
Bit 8
Undefined
Bit 9: shutter (AUR355C only)
0: OFF
1: ON
Bit 10
Undefined
Bits 11 to 13: flame level (AUR355C only)
0 to 5
Bits 14 to 15
Undefined
Recorded data 0.1 s after trigger 8101 x Bits 0 to 7: operating status No. when an
event occurs
Operating status No. table
(p.36)
Bits 8 to 15: flame voltage
0 to 50 [0.1 V]
x
Recorded data 10.0 s after trigger 8298 x Address: same as 8100
Recorded data 10.0 s after trigger 8299 x Address: same as 8101
* Settings can also be changed using Smart Loader Package model SLP-A55.