Azbil AUR450C - Subbase Terminal Block Connections; Flame Voltage Terminal Identification

Azbil AUR450C
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-8
Chapter 1. OVERVIEW
Terminal block signals
z Subbase terminal block
The table below describes the terminals on the subbase.
Terminal No. Description Rated
1 Model AUD300C/500C terminal F (blue)
2 Model AUD300C/500C terminal G (yellow)
3 Unused
4 Unused
5 Unused
6 Unused
7 Model AUD300C/500C shutter (white) 24 V DC 150 mA
8 Model AUD300C/500C shutter (white)
9 External reset input
10
11 Alarm output contact 75 VA max.
12
13 Power supply (H) 100/120/200/230 V AC
50/60 Hz
(depending on model No.)
14 Power supply (G)
15 Start contact input Contact resistance 100 Ω
max.
16 Start contact input
17 Interlock 100/120/200/230 V AC
50/60 Hz
Contact resistance 100 Ω
max.
18 Interlock
19 Ignition transformer 300 VA max. (cos φ = 0.5)
20 Main valve 200 VA max. (cos φ = 0.5)
21 Intermittent pilot 200 VA max. (cos φ = 0.5)
22 Interrupted pilot 200 VA max. (cos φ = 0.5)
23 Flame monitor output 75 VA max. (cos φ = 0.5)
24 Flame monitor output
z Flame voltage terminals
The table below describes the flame voltage terminals on the front panel.
Terminal No. Description Rated
+ Flame voltage output (+) 0 to 5 V DC *
- Flame voltage output (-)
* The flame voltage may reach approx. 7 V during self-discharge.