1-4
Chapter 1. OVERVIEW
Related devices
The table below shows the devices that can be used with this device.
Item Name Model No. or parts No. Remarks
Compatible base Subbase Q241A104 -20 to +60 °C AWG14 to 18
Compatible flame detector Advanced Ultraviolet Flame
Detector
AUD300C -20 to +120 °C IV wire 2.0 mm
2
AUD500C
(explosion-proof)
-20 to +60 °C 0.75 mm
2
cable
with silicone rubber insulation
Optional parts Flame simulator FSP300BC100 -
Analog flame meter FSP136A100 -
Surge absorber 83968019-001 -
Communications connector 81446848-001 1 piece
Loader Smart loader package SLP-A00J50 -
Certificates
• UL: File No. MH27717
• CE: Gas Appliance Directive (2009/142/EC) 0063BS1427
Low Voltage Directive (2014/35/EU)
Electromagnetic compatibility Directive (2014/30/EU)
RoHS Directive (2011/65/EU)
• FM: File No. 0003059531
Certificates are valid only for a combination of AUR450C, AUD300C, and
Q241A104.
Names and functions of parts
z Controller
7-segment display
Displays sequence codes,
alarm codes, event codes
and ame voltage.
LED indicators
Indicates current status of the
system.
Controller subbase screw
After the controller is placed on the subbase,
it is secured with this screw.
Switches between sequence code and ame voltage display.
RST switch
Resets the alarm (lockout).
ADDRESS switch
Sets the device's communications address.
RS-485 communications connector
Communications connector.
Loader jack
Connects to a personal computer
using a dedicated cable, when using
the PC Smart Loader program.
For the use of the loader, refer to;
User’s manual for Smart Loader Package Model SLP-A45
for Dynamic Self-Checking Burner Controller Model AUR450C
CP-SP-1187E.
Flame voltage terminals
Used for monitoring the ame voltage
Note: When the EVENT LED is lit, the event code can be
displayed.
All active events can be cleared at the same
time by pressing the DISP button for 2 s or
longer.
POWER
EVENT
SHUTTER
FLAME
ALARM
START
IG
PV
MV
RST
DISP
FLAME
VOLTAGE
ADDRESS
LOADER
RS-485
DYNAMIC SELF CHECK
BURNER CONTROLLER
AUR450
Note
•
There are covers on the RS-485 communications connector, loader jack, and
flame voltage terminals. For purposes of explanation, covers are not shown in the
above drawing.