EasyManua.ls Logo

Azbil AUR450C - Intermittent Pilot Internal Block Diagrams

Azbil AUR450C
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-11
Chapter 3. OPERATION
Internal block diagram
The internal block diagram below shows an example of wiring with external devices.
1413
1
10
12
11
24
23
K6
Flame output
K5
Alarm output
AUD300C/500C
(ame detector)
2
K6
K2
K2
K7
K3
K4
Shutter-driving
circuit
External reset
input circuit
8
9
Flame
amplifying
circuit
18
16
F
SR
G
Intermittent pilot valve 2
Ignition transformer
Intermittent pilot valve 1
21
22
20
19
External reset
input
*3
*3
AUR450C (for intermittent pilot burner)
Blue
Yellow
White
White
113X
Alarm relay
Pilot burner
for starting the
burner controller *2
7
K1
Input circuit
15
Burner start
contacts
Prepurge
end
Emergency
stop circuit
Blower on-o circuit
and prepurge circuit
Gas pressure upper
limit interlock
Gas pressure lower
limit interlock
(Interlock/
Limit contacts)
Vibration detection
limit
Overtemperature
limit
Air pressure lower
limit interlock
*1
113X
14
1
10
12
11
24
23
K6
Flame output
K5
Alarm output
AUD300C/500C
(ame detector)
2
K6
K2
K2
K7
K3
K4
Shutter-driving
circuit
External reset
input circuit
8
9
Flame
amplifying
circuit
F
G
22
20
19
External reset
input
AUR450C (for main burner)
Blue
Yellow
White
White
123X
Alarm relay
7
Main valve 2
K1
Main Burner start
contacts
123X
21
Main valve 1
Fuse
Fuse
High potential
side (H)
Low potential
side (G)
17
Power supply circuit
Fuse
13
18
16
R S
Input circuit
15
17
Power supply circuit
Fuse
Interlock
input circuit
Interlock
input circuit

Table of Contents