2-6
Chapter 2. MOUNTING AND WIRING
Do not use unused terminals as relay terminals.
Use an overload prevention device for the power supply as needed.
For wiring to the power source, use a 0.75 mm
2
wire (30 cores, 0.18 mm dia.) in
keeping with JIS C3306.
Terminal screws for the external reset input (terminal numbers 9 and 10) are
not assembled. When using the external reset input, wire to the subbase using
the included terminal screws.
For the external reset input signal and flame voltage output signal, use IV wire
0.75 mm
2
in cross-sectional area. Wire length should be 10 m max.
Be sure to set up a separate external reset input for each device. The external
reset input of another device cannot be shared.
Although terminals with a ground mark are provided on the subbase, this de-
vice is not grounded.
z Connecting to a surge absorber
When using the optional surge absorber as a protective measure against lightning,
connect it as shown below.
Model No.: 83968019-001 (sold separately)
(H)
(G)
Power supply Power supply
Flat terminal, FS4.8-series terminal side
Surge absorber between power line
13
14
13
14
Mounting bracket
Terminal
Surge absorber
83968019-001
Handling Precautions
Connect an FS4.8 series flat connector (AMP’s #187 series receptacle or equiva-
lent) to one end of the electric cable, keeping the wiring as short as possible.
Connect Mounting bracket of the surge absorber 83968019-001 to the metal
part such as the burner grounded.