3-3
Chapter 3. SP/EV BANK SETTINGS
Loop 1 recipe bank (L 1.rec)
Display
Loop number
and SP group
(
auxiliary display
)
Item Settings and descriptions Initial
value
User
setting
Remarks
SP 1.0 1.
LSP SP low limit to SP high limit 0 The decimal point position is
determined by the decimal point
position for the loop PV/SP.
E0 1 1.0 1.
Event 1 main setting -19999 to +32000 U 0 The decimal point position is
determined by the decimal
point position for the event
configuration.
E0 1.SB 1.0 1.
Event 1 sub setting
E02 1.0 1.
Event 2 main setting
E02.SB 1.0 1.
Event 2 sub setting
E03 1.0 1.
Event 3 main setting
E03.SB 1.0 1.
Event 3 sub setting
E04 1.0 1.
Event 4 main setting
E04.SB 1.0 1.
Event 4 sub setting
E05 1.0 1.
Event 5 main setting
E05.SB 1.0 1.
Event 5 sub setting
E06 1.0 1.
Event 6 main setting
E06.SB 1.0 1.
Event 6 sub setting
E07 1.0 1.
Event 7 main setting
E07.SB 1.0 1.
Event 7 sub setting
E08 1.0 1.
Event 8 main setting
E08.SB 1.0 1.
Event 8 sub setting
P 1.0 1.
Proportional band 0.1 to 3200.0 % 5.0
I 1.0 1.
Integral time 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no integral control action
when set at 0, 0.0 or 0.00)
120 The decimal point position is
determined by the decimal
point position for the control
parameter.
D 1.0 1.
Derivative time 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no derivative control action
when set at 0, 0.0 or 0.00)
30
OL 1.0 1.
Output low limit -10.0 to +110.0 % 0.0
OH 1.0 1.
Output high limit 100.0
RE 1.0 1.
Manual reset 50.0
P-C 1.0 1.
Proportional band for cool side 0.1 to 3200.0 % 5.0
I -C 1.0 1.
Integral time for cool side 0 to 32000s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no integral control action
when set at 0, 0.0 or 0.00)
120 The decimal point position is
determined by the decimal
point position for the control
parameter.
D-C 1.0 1.
Derivative time for cool side 0 to 32000 s, 0.0 to 3200.0 s or 0.00 to
320.00 s (no derivative control action
when set at 0, 0.0 or 0.00)
30
OL 1.0 1.
Output low limit for cool side -10.0 to +110.0 % 0.0
OH 1.0 1.
Output high limit for cool side 100.0
OI 1.0 1.
Initial output of PID control 0.0
SP 1.02.
LSP Same as SP group 1 0 Same as SP group 1
E0 1 1.02.
Event 1 main setting 0
E0 1.SB 1.02.
Event 1 sub setting
E02 1.02.
Event 2 main setting
E02.SB 1.02.
Event 2 sub setting
E03 1.02.
Event 3 main setting
E03.SB 1.02.
Event 3 sub setting
E04 1.02.
Event 4 main setting
E04.SB 1.02.
Event 4 sub setting
E05 1.02.
Event 5 main setting
E05.SB 1.02.
Event 5 sub setting
E06 1.02.
Event 6 main setting
E06.SB 1.02.
Event 6 sub setting
E07 1.02.
Event 7 main setting
E07.SB 1.02.
Event 7 sub setting
E08 1.02.
Event 8 main setting
E08.SB 1.02.
Event 8 sub setting
P 1.02.
Proportional band 5.0
I 1.02.
Integral time 120
D 1.02.
Derivative time 30
OL 1.02.
Output low limit 0.0
OH 1.02.
Output high limit 100.0
RE 1.02.
Manual reset 50.0
P-C 1.02.
Proportional band for cool side 5.0
I -C 1.02.
Integral time for cool side 120
D-C 1.02.
Derivative time for cool side 30
OL.C 1.02.
Output low limit for cool side 0.0
OH.C 1.02.
Output high limit for cool side 100.0
OI 1.02.
Initial output of PID control 0.0