Azbil Corporation  Safety Guide
Model MTG11A/18A, MTG11B/18B, MTG14C vii
4-3 :  Pneumatic piping and electric work
 CATUTION
•  Pneumatic tubing should be sized so as not to 
cause dropping of air pressure when the control 
valve is in operation. Pneumatic tubing should 
have an allowance in bend (use specialized 
tool) and the parallel tubing should be clamped 
together.
•  Only qualied persons should do electrical 
work in accordance to electrical facility 
engineering standards.
•  Cable connections should be made to conform 
to the facility's conditions. A suitable adaptor 
or packing should be selected to suit the outer 
dimension of the completed installation.
•  When using seal tape on pneumatic tubing, do 
not apply tape on the rst two threads from 
the tip of connector. This may block the air 
passage and cause malfunction of the valve.
•  When using liquid packing (seize lock) on 
pneumatic tubing, care should be exercised 
so the liquid does not leak into tubing. It 
may block the air passage, resulting in valve 
malfunction.
•  Avoid electrical work in rainy weather or at a 
time of high humidity. Any intrusion of water 
into connector or terminal will cause rusting 
and electrical leakage.
•  Covers of accessories such as the positioner are 
provided with a seal packing (gasket). Exercise 
care so as not to misplace or lose them while 
electrical work is in progress.
•  Exercise care so as not to lose xing screws 
of accessories such as the positioner. When 
tightening screws, ensure that packing is in 
place and tighten screws with an even torque.
•  Cable threads and conduit seal should be 
tightened so as to ensure that water does not 
get in.
Y
Seal
tape