4.9 SYSTEM MENU STRUCTURE
4.9.1 System Parameters
Title Description
Change PIN Change the PIN to access the System Menu
Local System Status View the Status of the Local Console
Local Device Status View the Status of the Local Internal Devices
Local Line Status View the Status of each Line of the Console
Vendor Details View and Change the Vendor Contact details
System Parameters View and Adjust settings relating to the system
Line Parameters View and adjust settings relating to the Line and
relevant Outstation
RTC Adjustment Set the Real Time Clock
Exit Exit from System Menu
Title Default Value Description
Local Address 1 Sets the Network Address of the Local Panel
DTA Resetable No Reset Active DTA calls from Console
BBU Monitored Yes Battery Backup Fault Monitoring
DRS Enable N-Open ** DRS Enable Contacts set to Normally Open **
DRS PF Enable Yes Enable DRS Remote Units on Mains Power Failure
RTC in ScnSvr No Show Real Time Clock on ScreenSaver
Fault Silence No Temporarily disable Fault Sounder
IC Call Silence No Temporarily disable Incoming Call Sounder
Silence Timeout 480mins Timeout before Fault & Incoming Call Sounders
are reactivated
LCD Timeout 60secs Timeout for LCD to return to Screensaver
LCD Contrast 37% LCD contrast
Fault Repeat 480mins Timeout before Faults are reannounced
Warning Repeat 720mins Timeout before Warnings are reannounced
CH Type CH Type of Console Handset on Local Console
CH Name Main Console Name of local Console
CH Offhook 1 >1600uA Threshold for Handset Offhook
CH Onhook 1 <9600uA Threshold for Handset Onhook
CH EOLz OC 1 <400uA Threshold for Open Circuit Handset Fault
CH EOLz SC 1 >46400uA Threshold for Short Circuit Handset Fault
Restore Defaults N/A Restore All System Settings to Default Values
Exit Exit System Parameters Menu
** This setting must be set to N-Closed when a Fire Panel Interface is required