7.7.4 “Local Loop” - Local Console Fault
The Front Panel cannot detect the correct number of internal
devices (C2CK4 Line Cards & C2CN Network Cards) to match
the stored configuration.
7.7.5 “Lo Z” - Line Fault - Local Console Fault
The console has detected the Line Impedance has dropped below
the minimum threshold (potentially a Short Circuit).
7.7.6 “Hi Z” - Line Fault - Local Console Fault
The console has detected the Line Impedance has increased
beyond the maximum threshold (potentially an Open Circuit).
7.7.7 “NW Audio Loop” - Network Audio Fault
An Audio Fault has been detected on the network or the Audio
Network Loop is no longer intact due to an open or short circuit.
7.7.8 “NW Loop” - Network Data Fault
A Data Fault has been detected on the network or the Data
Network Loop is no longer intact due to an open or short circuit.
7.7.9 Deep Discharge (Low Voltage) Protection
The Internal Power Supply will disconnect the batteries if they
discharge below 21V.