7.4 FAULTS ANNOUNCED WHILE “IN CALL
If a fault is announced while the Console is “In Call” it will not be
displayed on the LCD Display, however the buzzer will sound and
the “Common Fault” LED will flash.
Press and hold the encoder to silence the buzzer (this does not
accept the fault).
After the call is completed, replace the handset and close the
Handset door.
Scroll down and select the “Maintenance” menu and navigate to
the “Current Fault Status” page.
Any faults which have been announced but not accepted are
shown indicated with a “**”.
Scroll up or down to select faults showing the “**” and press and
hold the encoder to accept the faults.
7.5 VIEW FAULT HISTORY LOG
The Console will store the last 256 detected faults.
Close the Handset door.
Scroll down and select the “Maintenance” menu and navigate to
the “Fault History Log” page.
Scroll up or down to for the required entry and press the encoder.
The Location, Type of Fault and the Date stamp will be displayed.