6.5.2 Generic Wiring to FSDs (manual reset)
FSD
2
FSD
1
+24Vdc 0Vdc
Single-Channel
Safety Stop Circuit
Dual-Channel
Safety Stop Circuit
RESET/OR1**
BN* (Pin#2) +24V dc
GN/YE (#3) GND/PE
BU (#7) 0V dc
BK (#11) OSSD1
+
WH (#1) OSSD2
+
VI (#12)
OR (#9) EDM
PK (#6)
OR2/ME**
YE (#4) M1
GY (#5) M2
RD (#8) AUX/FAULT
+
Figure 26. Generic hookup - FSDs (1-CH EDM, manual reset, Override)
Note: *Color code reflects RDLP-11..E and DELPE-12..E cordsets and pin out. Pin #10 on M12/Euro-style
QD not used. See
Cordsets
(p. 82) for further cordset information.
** For Trip (auto reset) operation VI (#12) is not connected. If override (bypass) is not used PK (#6) must
be connected to +24 V dc.
+ Do not exceed OSSD maximum load capacitance specification. See
Specifications
(p. 14).