6.5.3 IM-T-9A
BK (#11) OSSD1
WH (#1) OSSD2
OR (#9) EDM
+24Vdc
0Vdc
BN* (Pin#2) +24V dc
GN/YE (#3) GND/PE
BU (#7) 0V dc
PK (#6)
OR2/ME**
Y E (#4) M1
GY (#5) M2
RD (#8) AUX/FAULT
+
13
Y2
IM -T -9A
14
Y1
K1
K2
23
33
24
34
S3
S1
S4
S2
Y3
Y4
Machine
Control
Feedback (optional)
MPCE
1
MPCE
2
RESET/OR1**
VI (#12)
***
Figure 27. Generic hookup - Interface Module (1-CH EDM, manual reset, Override)
Note: * Color code reflects RDLP-11..E and DELPE-12..E cordsets and pin out. Pin #10 on M12/Euro-
style QD not used. See
Cordsets
(p. 82) for further cordset information.
** For Trip (auto reset) operation VI (#12) is not connected. If override (bypass) is not used PK (#6) must
be connected to +24 V dc.
*** Installation of transient (arc) suppressor across the coils of MPCE1 and MPCE2 is recommended (see
Warning).
WARNING:
Properly install arc or transient suppressors
Failure to follow these instructions could result in serious injury or death.
Install any suppressors as shown across the coils of the machine primary control elements. Do
not install suppressors directly across the output contacts of the safety or interface module. In
such a
configuration, it is possible for suppressors to fail as a short circuit.
EZ-SCREEN Low-Profile System with Integral Muting
48 www.bannerengineering.com - Tel: + 1 888 373 6767