Icon Fault Code Device Status
OSSD
Status
Description
!
INTF11
INTF11 Lockout Off
FPGA integrity test failure - Internal self test failure.
Reset the system using the reset function or cycle the power to the device.
Try using a separate filtered power supply and/or a grounded shielded cable
to connect the scanner to the cabinet to eliminate external causes of the
failure. If the failure persists, contact the factory for support.
!
INTF12
INTF12 Lockout Off
FPGA power supply supervisor failure.
Reset the system using the reset function or cycle the power to the device.
Try using a separate filtered power supply and/or a grounded shielded cable
to connect the scanner to the cabinet to eliminate external causes of the
failure. If the failure persists, contact the factory for support.
!
INTF13
INTF13 Lockout Off
Measurement integrity test failure - Internal target coherence test.
Reset the system using the reset function or cycle the power to the device.
Try using a separate filtered power supply and/or a grounded shielded cable
to connect the scanner to the cabinet to eliminate external causes of the
failure. If the failure persists, contact the factory for support.
!
INTF14
INTF14 Lockout Off
Temperature measurement integrity check - Coherence comparison of
sensors.
Switch off the scanner and check the temperature of the environment. Allow
the scanner to cool for 10-15 minutes, then turn the scanner back on.
If the failure persists, contact the factory for support.
!
INTF15
INTF15 Lockout Off
Rotational speed coherence test failure.
Contact the factory for support.
!
INTF16
INTF16 Lockout Off
Dust detector integrity failure.
Reset the system using the reset function or cycle the power to the device.
Try using a separate filtered power supply and/or a grounded shielded cable
to connect the scanner to the cabinet to eliminate external causes of the
failure. If the failure persists, contact the factory for support.
!
INTF17
INTF17 Lockout Off
Power supervisory failure.
Reset the system using the reset function or cycle the power to the device.
Try using a separate filtered power supply and/or a grounded shielded cable
to connect the scanner to the cabinet to eliminate external causes of the
failure. If the failure persists, contact the factory for support.
!
INTF18
INTF18 Lockout Off
Internal failure.
Reset the system using the reset function or cycle the power to the device.
Try using a separate filtered power supply and/or a grounded shielded cable
to connect the scanner to the cabinet to eliminate external causes of the
failure. If the failure persists, contact the factory for support.
This fault also occurs when a device in the master/remote cluster is
replaced or removed (topology fault). If this is the case, connect to the
configuration software and upload a new configuration.
!
INTF20
INTF20 Normal Off
Master/remote connection failure.
Check the network connector of the integrity of the remote devices and
restore normal network operation.
If the failure persists, contact the factory for support.