Manual 2100-684
Page 15 of 25
No.
Unit
Type
CompleteStat
Model
CS9B(E)-
1
CompleteStat
System Type
System
Stages
Setting
Economizer
Setting
Use with
Bard Units
Ventilation System
Vent
Control
Type
1 A/C THOA, THOCA A/C 2H/2C None
1 or 2-Stage A/C w/ or
w/o Elec. Heat
CRV, ERV, MFAD On/Off
2 A/C THOA, THOCA A/C 2H/2C EN/DIS
1-Stage A/C with or
w/o Elec. Heat
ECONWM Factory "T"
or "W" Economizer w/
JADE W7220 Control
On/Off
3 A/C THOA, THOCA A/C 2H/2C EN/DIS
2-Stage A/C with or
w/o Elec. Heat
ECONWM Factory "T"
or "W" Economizer w/
JADE W7220 Control
On/Off
4 HP THOA, THOCA HP 1 Stage None
1-Stage HP with or
w/o Elec. Heat
CRV, ERV, MFAD On/Off
5 HP THOA, THOCA HP 2 Stage None
2-Stage HP with or
w/o Elec. Heat
CRV, ERV, MFAD On/Off
6 HP THOA, THOCA HP 1 Stage EN/DIS
1-Stage HP with or
w/o Elec. Heat
ECONWM Factory "T"
or "W" Economizer w/
JADE W7220 Control
On/Off
7 HP THOA, THOCA HP 2 Stage EN/DIS
2-Stage HP with or
w/o Elec. Heat
ECONWM Factory "T"
or "W" Economizer w/
JADE W7220 Control
On/Off
8 Gas/Electric THOA, THOCA A/C 1H/1C None
1-Stage A/C with Gas
Heat
CRV, ERV, MFAD On/Off
9 Gas/Electric THOA, THOCA A/C 1H/2C None
2-Stage A/C with Gas
Heat
CRV, ERV, MFAD On/Off
10 I-TEC
®
HP THOA, THOCA HP 2 Stage None
2-Stage HP with or
w/o Elec. Heat
None On/Off
11 I-TEC
®
HP THOA, THOCA HP 2 Stage None
2-Stage HP with or
w/o Elec. Heat
CRV On/Off
12 I-TEC
®
HP THOA HP 2 Stage None
2-Stage HP with or
w/o Elec. Heat
Modulating ERV, use
–THOA plus 8403-
067 CO
2
controller
Mod.
2
13 Q-TEC
TM
QA THOA, THOCA A/C 2H/1C None
1-Stage A/C with or
w/o Elec. Heat
CRV, ERV On/Off
14 Q-TEC
TM
QH THOA, THOCA HP 1 Stage None
1-Stage HP with or
w/o Elec. Heat
CRV, ERV On/Off
15 QWS THOA, THOCA HP 2 Stage None
2-Stage Geo/Water
Source HP
CRV, ERV On/Off
16 C**H THOA, THOCA HP 2 Stage EN/DIS
2-Stage HP with or
w/o Elec. Heat
ECONCH Factory
“S” w/JADE W7220
Control
On/Off
WIRING DIAGRAMS
TABLE 8
Wiring Diagram Index
1
Either THOA or THOCA version can be used. For THOA, vent output “A” limits vent operation to occupied periods. For THOCA, vent
output “A” operates vent based on CO
2
level.
2
Modulating