EasyManuals Logo

Basler DECS-150 User Manual

Basler DECS-150
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #178 background imageLoading...
Page #178 background image
24-4 9492600990
Testing DECS-150
CompF: Compensated Frequency
Deviation
ErrIn: AVR Error Signal
FcrErr
FcrOut
G/M Hz: Generator/Motor Frequency {Hz}
I1: Positive Sequence Current {pu}
I2: Negative Sequence Current {pu}
Ia: Phase A Current {pu}
Iaux: Cross Current Input {pu}
Iavg: Ave Line Current{pu}
Ib: Phase B Current {pu}
Ic: Phase C Current {pu}
Ifd: Field Current {pu}
kVA: Total Power {pu}
kvar: Reactive Power {pu}
kW: Real Power {pu}
MechP: Filtered Mechanical Power
Network Load Share
NullBalance: Null Balance Level
OelOutput: OEL Controller Output
PF: Power Factor
Post: Post-Limit Output {pu}
POut: Final PSS Output {pu}
Prelim: Pre-Limit Output {pu}
PsskW: PSS Electric Power {pu}
Ptest: Time Response Signal {pu}
SclOutput: SCL Controller Output
Synth: Synthsized Speed {pu}
TermF: Terminal Frequency Deviation
Test: Frequency Response Signal {pu}
Tflt1: Torsional Filter #1 {pu}
TrnOp: Internal State {pu}
UelOutput: UEL Controller Output
V1: Positive Sequence Voltage {pu}
V2: Negative Sequence Voltage {pu}
Vab: PhA-PhB L-L Voltage {pu}
Var/PfErr
Var/PfOut
Vaux: Aux Voltage Input {pu}
Vavg: Ave L-L Voltage {pu}
Vbc: PhB-PhC L-L Voltage {pu}
Vbus: Bus Voltage {pu}
Vca: PhC-PhA L-L Voltage {pu}
Vfd: Field Voltage {pu}
Vtmag: PSS Term Voltage
WashP: Washed Out Power
WashW: Washed Out Speed {pu}
x10: Mechanical Power LP #3
x11: Mechanical Power LP #4
x15: Lead-Lag #1 {pu}
x16: Lead-Lag #2 {pu}
x17: Lead-Lag #3 {pu}
x2: Speed HP #1
x29: Torsional Filter #2 {pu}
x31: Lead-Lag #4 {pu}
x5: Power HP #1 {pu}
x7: Mechanical Power {pu}
x8: Mechanical Power LP #1
x9: Mechanical Power LP #2
Frequency Response
Read-only frequency response fields indicate the magnitude response, phase response, and test signal
frequency. The magnitude response and phase response corresponds to the test signal previously
applied. The test frequency value reflects the frequency of the test signal currently being applied.
Caution
Exercise caution when performing frequency response testing on a
generator connected to the grid. Frequencies that are close to the
resonant frequency of the machine or neighboring machines are to be
avoided. Frequencies above 3 Hz may correspond to the lowest shaft
torsional frequencies of a generator. A torsional profile for the machine
should be obtained from the manufacturer and consulted before
conducting any frequency response tests.
Time Response
Tests should be performed at various load levels to confirm that the input signals are calculated or
measured correctly. Since the PSS function uses compensated terminal frequency in place of speed, the
derived mechanical power signal should be examined carefully to ensure that it does not contain any
components at the electromechanical oscillation frequencies. If such components are present, it indicates
that the frequency compensation is less than ideal, or that the machine inertia value is incorrect.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler DECS-150 and is the answer not in the manual?

Basler DECS-150 Specifications

General IconGeneral
BrandBasler
ModelDECS-150
CategoryControl Systems
LanguageEnglish

Related product manuals