Loading...
9492600990 25-11
DECS-150 Modbus
®
Communication
Group
Name
Register
Type
Bytes
R/W
Unit
Range
Configurable Element 7
Alarm Configuration
185
Uint32
4
R W
n/a
Status Only=0
Alarm=1
Configurable Element 7
Activation Delay
187
Uint32
4
R W
Second
0–300
Configurable Element 8
Contact Recognition
189
Uint32
4
R W
n/a
Always=0
Alarm=1
Configurable Element 8
Alarm Configuration
191
Uint32
4
R W
n/a
Status Only=0
Alarm=1
Configurable Element 8
Activation Delay
193
Uint32
4
R W
Second
0–300
Security
Table 25-5. Security Group Parameters
Group
Name
Register
Type
Bytes
R/W
Range
Security
Secure Login
500
String
34
RW
0–34
Security
Logout
517
String
5
RW
0–5
Security
Current Access
520
Uint32
4
R
No Access=0
Read Access=1
Control Access=2
Operator Access=3
Setting Access=4
Design Access=5
Administrator Access=6
Security
Save Changes
522
Uint32
4
R W
n/a
Binary Points
Table 25-6. Binary Point Group Parameters
Group
Name
Register
Type
Bytes
R/W
Range
Alarms
Firmware Change Alarm
900 bit 0
Uint16
2
R
True=1 False=0
Alarms
Ethernet Link Lost Alarm
900 bit 1
Uint16
2
R
True=1 False=0
Alarms
Logic Equal None Alarm
900 bit 2
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 1
900 bit 3
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 2
900 bit 4
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 3
900 bit 5
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 4
900 bit 6
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 5
900 bit 7
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 6
900 bit 8
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 7
900 bit 9
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 8
900 bit 10
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 9
900 bit 11
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 10
900 bit 12
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 11
900 bit 13
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 12
900 bit 14
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 13
900 bit 15
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 14
901 bit 0
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 15
901 bit 1
Uint16
2
R
True=1 False=0
Alarms
Programmable Alarm 16
901 bit 2
Uint16
2
R
True=1 False=0
Alarms
Underfrequency V/Hz Alarm
901 bit 3
Uint16
2
R
True=1 False=0
Alarms
OEL Alarm
901 bit 4
Uint16
2
R
True=1 False=0
Alarms
UEL Alarm
901 bit 5
Uint16
2
R
True=1 False=0
Alarms
SCL Alarm
901 bit 6
Uint16
2
R
True=1 False=0
Alarms
Power Supply Low Alarm
901 bit 7
Uint16
2
R
True=1 False=0
Alarms
PSS Voltage Unbalanced Alarm
901 bit 8
Uint16
2
R
True=1 False=0
Alarms
PSS Current Unbalanced Alarm
901 bit 9
Uint16
2
R
True=1 False=0
Alarms
PSS Power Below Threshold Alarm
901 bit 10
Uint16
2
R
True=1 False=0
Alarms
PSS Speed Failed Alarm
901 bit 11
Uint16
2
R
True=1 False=0