9492600990 25-13
DECS-150 Modbus
®
Communication
Group
Name
Register
Type
Bytes
R/W
Range
DECS Control
Manual Active
904 bit 15
Uint16
2
R
True=1 False=0
DECS Control
Auto Active
905 bit 0
Uint16
2
R
True=1 False=0
DECS PSS Meter
PSS Active
905 bit 1
Uint16
2
R
True=1 False=0
DECS Regulator Meter
Setpoint at Lower Limit
905 bit 2
Uint16
2
R
True=1 False=0
DECS Regulator Meter
Setpoint at Upper Limit
905 bit 3
Uint16
2
R
True=1 False=0
DECS Regulator Meter
Internal Tracking Active
905 bit 4
Uint16
2
R
True=1 False=0
DECS Regulator Meter
External Tracking Active
905 bit 5
Uint16
2
R
True=1 False=0
Field Overvoltage
Pickup
905 bit 6
Uint16
2
R
True=1 False=0
Field Overvoltage
Trip
905 bit 7
Uint16
2
R
True=1 False=0
Loss of Sensing
Pickup
905 bit 8
Uint16
2
R
True=1 False=0
Loss of Sensing
Trip
905 bit 9
Uint16
2
R
True=1 False=0
EDM
Pickup
905 bit 10
Uint16
2
R
True=1 False=0
EDM
Trip
905 bit 11
Uint16
2
R
True=1 False=0
25 Element
Status
905 bit 12
Uint16
2
R
True=1 False=0
27P Element
Block
905 bit 13
Uint16
2
R
True=1 False=0
27P Element
Pickup
905 bit 14
Uint16
2
R
True=1 False=0
27P Element
Trip
905 bit 15
Uint16
2
R
True=1 False=0
59P Element
Pickup
906 bit 0
Uint16
2
R
True=1 False=0
59P Element
Trip
906 bit 1
Uint16
2
R
True=1 False=0
81-1 Element
Pickup
906 bit 2
Uint16
2
R
True=1 False=0
81-1 Element
Trip
906 bit 3
Uint16
2
R
True=1 False=0
81-2 Element
Pickup
906 bit 4
Uint16
2
R
True=1 False=0
81-2 Element
Trip
906 bit 5
Uint16
2
R
True=1 False=0
Gen Below 10 Hz
Pickup
906 bit 6
Uint16
2
R
True=1 False=0
Gen Below 10 Hz
Trip
906 bit 7
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 1 Pickup
906 bit 8
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 1 Trip
906 bit 9
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 2 Pickup
906 bit 10
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 2 Trip
906 bit 11
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 3 Pickup
906 bit 12
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 3 Trip
906 bit 13
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 4 Pickup
906 bit 14
Uint16
2
R
True=1 False=0
Configurable Protection 1
Configurable Protection Threshold 4 Trip
906 bit 15
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 1 Pickup
907 bit 0
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 1 Trip
907 bit 1
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 2 Pickup
907 bit 2
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 2 Trip
907 bit 3
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 3 Pickup
907 bit 4
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 3 Trip
907 bit 5
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 4 Pickup
907 bit 6
Uint16
2
R
True=1 False=0
Configurable Protection 2
Configurable Protection Threshold 4 Trip
907 bit 7
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 1 Pickup
907 bit 8
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 1 Trip
907 bit 9
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 2 Pickup
907 bit 10
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 2 Trip
907 bit 11
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 3 Pickup
907 bit 12
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 3 Trip
907 bit 13
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 4 Pickup
907 bit 14
Uint16
2
R
True=1 False=0
Configurable Protection 3
Configurable Protection Threshold 4 Trip
907 bit 15
Uint16
2
R
True=1 False=0
Configurable Protection 4
Configurable Protection Threshold 1 Pickup
908 bit 0
Uint16
2
R
True=1 False=0
Configurable Protection 4
Configurable Protection Threshold 1 Trip
908 bit 1
Uint16
2
R
True=1 False=0