28-6 9492600990
Specifications DECS-150
On-Line Overexcitation Limiting
High Current Level
Pickup
Range 0 to 11 Adc (70°C ambient) or 0 to 14 Adc (55°C ambient)
Increment ......................................... 0.01 Adc
Time
Range 0 to 10 s
Increment ......................................... 1 s
Medium Current Level
Pickup
Range 0 to 9 Adc (70°C ambient) or 0 to 12 Adc (55°C ambient)
Increment ......................................... 0.01 Adc
Time
Range 0 to 120 s
Increment ......................................... 1 s
Low Current Level
Pickup
Range 0 to 7 Adc (70°C ambient) or 0 to 10 Adc (55°C ambient)
Increment ......................................... 0.01 Adc
Off-Line Overexcitation Limiting
High Current Level
Pickup
Range 0 to 11 Adc (70°C ambient) or 0 to 14 Adc (55°C ambient)
Increment ......................................... 0.01 Adc
Time
Range: 0 to 10 s
Increment: ........................................ 1 s
Low Current Level
Pickup
Range 0 to 7 Adc (70°C ambient) or 0 to 10 Adc (55°C ambient)
Increment ......................................... 0.01 Adc
Sequence of Events Recording (SER)
See the Reports section.
Data Logging (Oscillography)
See the Reports section.