28-8 9492600990
Specifications DECS-150
Terminals.......................................... CAN 2 H, L, SH
Communication Rate ........................ 250 kb/s
Environment
Temperature
Operating Range
7 Adc Continuous ...................... –40 to +70°C (–40 to +158°F)
10 Adc Continuous .................... –40 to +55°C (–40 to +131°F)
Storage Range ................................. –40 to +85°C (–40 to +185°F)
Humidity
Complies with MIL-STD-705B, Method 711-1C
Salt Fog
Complies with IEC 60068-2-11
Elevation
1,000 m (3,300 ft.) maximum
Ingress Protection
Front-Panel USB Port (Style xxS2V) ...... IP42
Rear-Panel USB Port (Style xxS1V) ....... IP54
Type Tests
Shock
Withstands 30 G in 3 perpendicular planes.
Vibration
18 to 2,000 Hz .................................. 5 G for 3 hours
Transients
EN61000-4-4
Static Discharge
EN61000-4-2
HALT (Highly Accelerated Life Testing)
HALT is used by Basler Electric to prove that our products will provide the user with many years of
reliable service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate
years of operation, but in a much shorter period. HALT allows Basler Electric to evaluate all possible
design elements that will add to the life of this device. As an example of some of the extreme testing
conditions, the DECS-150 was subjected to temperature tests (tested over a temperature range of −90 to
+130°C (−130 to +202°F)),
vibration tests (of 5 to 50 G at +20°C (68°F)), and temperature/vibration tests
(tested at 50 G over a temperature range of −80 to +120°C (−112 to +248°F)). Combined temperature
and vibration testing at these extremes proves that the DECS-150 is expected to provide long-term
operation in a rugged environment. Note that the vibration and temperature extremes listed in this
paragraph are specific to HALT and do not reflect recommended operation levels.