EasyManua.ls Logo

Basler DECS-250 - Page 90

Basler DECS-250
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12-10 9440300990
Grid Code DECS-250
Figure 12-9. Reactive Power Control, Q(U) Screen
Reactive Power as a Function of Active Power Q(P)
BESTCOMSPlus Navigation Path: Settings Explorer, Grid Code Settings, Reactive Power Control, Q(P)
HMI Navigation Path: Settings, Operating Settings, Grid Code Settings, Reactive Power Control, Q(P)
Settings
In this mode the reactive power output of the machine is adjusted as the real power output fluctuates
(Q = f(P)).
A filter time constant setting is available for the measured power level. The characteristic curve is
specified by up to 10 points relating desired Q output to exported power. Perform linear interpolation
between the points. The active power coordinate for each point may range from 10% to 100% active
power and the range for the reactive power level must conform to Figure 12-10, below. Above 20% active
power, the reactive power range should be -0.33 to 0.33 per unit reactive power.
Figure 12-10. Q(P) Characteristic Curve
Figure 12-11 illustrates an example characteristic with five plotted points.

Related product manuals