25
7.7.
Macro Functions - Keypad Mode (P-12 = 1 or 2)
-------------------------------------
-------------------------------
7.8. Macro Functions - Fieldbus Control Mode (P-12 = 3, 4, 7, 8 or 9)
FB REF (Fieldbus Speed Reference, Modbus RTU / CAN / Master
7.9. Macro Functions - User PI Control Mode (P-12 = 5 or 6)
7.10. Fire Mode
The Fire Mode function is designed to ensure continuous operation of the drive in emergency conditions until the drive is no longer capable of
sustaining operation. The Fire Mode input must be closed for normal operation – removing the signal from this input will cause the drive to
enter Fire Mode. This input may be linked to a fire control system, so that in the event of a fire in the building and drive operation is required
to be maintained for the longest possible period in order to clear smoke or maintain air quality within that building.
The fire mode function is enabled when P-15 = 14 or 15, with Digital Input 3assigned to activate fire mode.
Fire Mode disables the following protection features in the drive:- O-t (Heat-sink Over-Temperature), U-t (Drive Under Temperature), Th-FLt
(Faulty Thermistor on Heat-sink), E-trip (External Trip), 4-20 F(4-20mA fault), Ph-Ib (Phase Imbalance), P-Loss (Input Phase Loss Trip), SC-trp
(Communications Loss Trip), I_t-trp (Accumulated overload Trip)
The following faults will result in a drive trip, auto reset and restart:- O-Volt (Over Voltage on DC Bus), U-Volt (Under Voltage on DC Bus), h O-I
(Fast Over-current Trip), O-I (Instantaneous over current on drive output), Out-F (Drive output fault, Output stage trip)