EasyManua.ls Logo

Bender ISOMETER isoRW425 - Page 10

Bender ISOMETER isoRW425
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 isoRW425_D00052_06_Q_DEEN / 11.2023
ISOMETER® isoRW425
Connection
Connection type ................................. screw-type or push-wire terminal
Screw-type terminals:
Nominal current ...........................................................................≤ 10 A
Tightening torque .........................................0.5…0.6 Nm (5…7 lb-in)
Conductor sizes ..................................................................... AWG 24-12
Stripping length .............................................................................8 mm
Rigid/flexible ...................................................................0.2…2.5 mm²
Flexible with ferrules with/without plastic sleeve ..................................
.......................................................................................0.25…2.5 mm²
Multi-conductor rigid .......................................................0.2…1.5 mm²
Multi-conductor flexible ..................................................0.2…1.5 mm²
Multi-conductor flexible with ferrules without plastic sleeve .................
.......................................................................................0.25…1.5 mm²
Multi-conductor flexible with TWIN ferrules with plastic sleeve .............
.......................................................................................0.25…1.5 mm²
Push-wire terminals:
Nominal current ...........................................................................≤ 10 A
Conductor sizes ..................................................................... AWG 24-14
Stripping length ...........................................................................10 mm
Rigid ................................................................................0.2…2.5 mm²
Flexible without ferrules ................................................0.75…2.5 mm²
Flexible with ferrules with/without plastic sleeve ..................................
.......................................................................................0.25…2.5 mm²
Multi-conductor flexible with TWIN ferrules with plastic sleeve .............
.........................................................................................0.5…1.5 mm²
Opening force ..................................................................................50 N
Test opening, diameter ............................................................... 2.1 mm
Other
Operating mode ...................................................... continous operation
Mounting .............................. cooling slots must be ventilated vertically
Flammability class ....................................................................UL 94V-0
Degree of protection, built-in components (DIN EN 60529) .............IP30
Degree of protection, terminals (DIN EN 60529) ..............................IP20
Anschluss
Anschlussart ...............................................Schraub- oder Federklemme
Schraubklemmen:
Nennstrom ...................................................................................≤ 10 A
Anzugsmoment ............................................0,5…0,6 Nm (5…7 lb-in)
Leitergrößen ......................................................................... AWG 24-12
Abisolierlänge ................................................................................ 8 mm
Starr/flexibel ....................................................................0,2…2,5 mm²
Flexibel mit Aderendhülse mit/ohne Kunststoffhülse .............................
.......................................................................................0,25…2,5 mm²
Mehrleiter starr ................................................................0,2…1,5 mm²
Mehrleiter flexibel ...........................................................0,2…1,5 mm²
Mehrleiter flexibel mit Aderendhülse ohne Kunststoffhülse ...................
.......................................................................................0,25…1,5 mm²
Mehrleiter flexibel mit TWIN Aderendhülse ohne Kunststoffhülse .........
.......................................................................................0,25…1,5 mm²
Federklemmen:
Nennstrom ...................................................................................≤ 10 A
Leitergrößen ......................................................................... AWG 24-14
Abisolierlänge .............................................................................. 10 mm
Starr .................................................................................0,2…2,5 mm²
Flexibel ohne Aderendhülse ...........................................0,75…2,5 mm²
Flexibel mit Aderendhülse mit/ohne Kunststoffhülse .............................
.......................................................................................0,25…2,5 mm²
Mehrleiter flexibel mit TWIN Aderendhülse mit Kunststoffhülse ............
.........................................................................................0,5…1,5 mm²
Öffnungskraft ...................................................................................50 N
Testöffnung, Durchmesser ..........................................................2,1 mm
Sonstiges
Betriebsart ......................................................................... Dauerbetrieb
Einbaulage ..............Kühlschlitze müssen senkrecht durchlüftet werden
Entflammbarkeitsklasse ............................................................UL 94V-0
Schutzart Einbauten (DIN EN 60529) ...............................................IP30
Schutzart Klemmen (DIN EN 60529) ................................................IP20