Parameter settings
Alarm relay K1: Activating the category response value I2
Alarm relay K1: Deactivating the category ‘Alarm by device test’
CAUTION
When an alarm relay (K1/K2) has been deactivated in the menu, an alarm will not be signalled by the
respective changeover contact! An alarm will only be indicated by the respective alarm LED (AL1/AL2)!
5.5 Set the time delays
The following delays can be set
•
Response delay t
on1
(0…10 s) for K1, and t
on2
(0…10 s) for K2
•
Starting delay t (0…10 s) when the device is being started
•
Common delay on release t
off
(0…99 s) for K1, K2. The setting t
off
is only relevant when the fault memory M is
deactivated.
The operating steps for the setting of the response delay t
on1
and the starting delay t are illustrated by way of
example.
22 RCM420_D00057_06_M_XXEN/12.2023