LINETRAXX® RCM420
Option ‘W’ data different from the standard version
Classification of climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3)
3K23 (condensation and
formation of ice is possible)
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3)
3M12
Connection
For UL applications: Use copper wire only!
For UL applications: Use 60/70 °C copper conductors only!
Connection type screw-type terminals
rigid/flexible
0.2…4 / 0.2…2.5 mm
2
(AWG 24…12)
Connection
properties
multi-conductor connection (2 conductors with the same
cross section) rigid/flexible
0,2…1,5 / 0,2…1,5 mm
2
(AWG 24…16)
Stripping length 8…9 mm
Tightening torque 0.5…0.6 Nm
Connection type push-wire terminals
rigid 0.2…2.5 mm
2
(AWG 24…14)
flexible without ferrules 0.75…2.5 mm
2
(AWG 19…14)
Connection
properties
flexible with ferrules 0,2…1,5 mm
2
(AWG 24…16)
Stripping length 10 mm
Opening force 50 N
Test opening, diameter 2.1 mm
Other
Operating mode continuous operation
Position of normal use display oriented
Protection class, internal components (IEC 60529) IP30
Protection class, terminals (IEC 60529) IP20
Enclosure material polycarbonate
Flammability class UL94V-0
DIN rail mounting acc. to IEC 60715
Screw mounting 2 x M4 with mounting clip
Software version D240 V1.2x
RCM420_D00057_06_M_XXEN/12.2023 31