Before starting with the installation, the scope of delivery should be checked for
completeness in accordance with the enclosed delivery documents. Also see chapter 3,
Scope of delivery, page 17.
No liquids must be able to get into the inside of the charger.
The horizontal distance between the charger and combustible materials must be
at least 2.50 m. Both the storage of flammable materials and the use of
flammable construction materials above the charger is not permitted. The
clearance from areas that are at risk of fire or explosion must be at least 5 m.
The charger must be protected from impermissible stress. It is particularly
important for components not to be damaged during transportation and handling.
Contact with electronic components must be avoided. The charger corresponds
to the protection class; see type plate.
Space must be available to place the machine next to the charger.
Clearance of at least 30 cm must be maintained in the air supply and exhaust
areas.
The air supply must not be adversely affected by other devices (exhaust from
other devices etc.).
7.1.1 Subsurface
The subsurface must be able to bear the weight.
The subsurface must be even.
The subsurface must not be flammable.
7.2 Preparing components