19
Bentone B40 MF/B45-2 MF
For installers
X3
X4
1. Transport oil fi lter
2. Basket lter
3. Overfl ow valve 0.5 – 2.0 bar
4. Seal lter
5. Pressure gauge 1
6. Pressure gauge 2
3
2
1 Transport oil pump / Transportoljepump
4
5
6
1
!
If any electrical connection is used other than that recommended by Bentone, there may be a danger of
damage to property and personal injury.
2.3.2 Proposed pipe routing for oil distribution systems with transport
pump, basket fi lter and seal fi lter
2.4 Electrical connection
Before electrical installation begins, the main power switch must be turned off.
If the boiler has a 7-pole and a 4-pole Euro plug connector, they will usually
connect directly to the burner. Otherwise, use the supplied connectors. The
5-pole connector supplies the burner preheater with a separate 3-phase
supply. See connection under Electrical equipment.
1. Switch off the main switch.
2. Connect the Euro plugs. (See Electrical equipment)
3. Make sure the burner operations switch (S1) is off.
4. Turn on the main switch.