EasyManua.ls Logo

Bentone B40 MF - Technical Data LMO24.255

Bentone B40 MF
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
Bentone B40 MF/B45-2 MF
For installers
LMO24
Pre-ignition time: 25 sec
Pre-ventilation time 25 sec
Reconnection after tripping <1 sec
Ambient temperature from - 20 to + 60 °C
Min. current at flame: 45 μ A
Max. output at dark, start: 5.5 μ A
Enclosure type IP 40
Safety time 5 sec
Check of photo current
Photo current is measured using a DC ampmeter (torsion coil instrument)
connected in series with the photocell.
8.5 Technical data LMO24.255...