MANUAL OPERATION
Version: 6.1 (05-12-2011) 43
See also section 2.8.
54. Strength with door closed Set the minimum fan speed when contact is made with the
input. Use a door switch here to reduce the fan speed when
the door is closed.
This has an effect only when function 60. Function of input is
set to Quick speed up or Slow speed up.
55. Winter setting door If the difference between the desired and the actual room
temperature is larger than this value, contact is made. An
automatic sliding door can then be set to half open.
This has an effect only when function 61a/b. Function of output
1/2 is set to Winter setting door.
58. Maximum strength The maximum fan speed can be limited in order to limit the
noise level. This function has an effect only in Automatic
mode.
Use of this function can reduce the comfort.
60. Function of input The unit has one input which can be used to have a function
controlled by an external accessory such as a door switch,
thermostat or a signal from a building management system
(BMS).
If several units are connected to one control panel, only one
input can be used. The effect of this input is then the same for
all the units.
The function Unit OFF locally has an effect only on the units
whose inputs are in use.
When the timer is in use, the function All units ON/OFF of the
input on the unit is deactivated, irrespective of this setting.
With the setting All units OFF and with the NC (normally
closed) settings, a jumper must be laid to the input for all the
other connected units.
See also section 2.8.
61a/b. Function of output 1/2 The unit has an interface for two output signals: These can be
used, for example, for controlling the central heating or
cooling system, or for transmitting status reports to a BMS.
The outputs function independently of one another.