EasyManua.ls Logo

Biddle HR 25 - Page 26

Default Icon
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION HEAT RECOVERY UNIT
en-26
en
Unit output
The unit has an output signal interface (X3). A warning lamp
for dirty filters can be connected to this.
Caution:
c Keep the cable length to a maximum of 3 metres.
2.11.2 Installing smoke detector or fire alarm (acces-
sory)
In emergencies, the unit can emit an alarm signal or even
actively deal with the problem by functioning in a special
mode. (See menu > Configuration > 60. Function of inputs)
This function can be activated by the building management sys-
tem (register address 435) or by an external sensor.
If an external sensor is used:
1. Place a smoke detector or fire alarm (not supplied) at
a
su
itable location.
2. Without using the power supply (230V) from the unit:
- Connect the sensor to X3 1 in the electronics mod-
ule in accordance with the wiring diagram
3. Using the power supply (230V) from the unit:
- Connect the sensor to X1 2 in the electronics mod-
ule in accordance with the wiring diagram
- Place a bridge between X1 and X3
Note:
n When starting the unit, indicate what response must
be given to a signal from the sensor. (Via the b-touch
control panel: menu > Configuration > 60. Function
of inputs or via the building management system:
register address 337 Alarm functions)