EasyManua.ls Logo

Biddle HR 25 - Page 67

Default Icon
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HR MANUAL SERVICE
Manual version 4.1 (26-07-2018)
en-67
en
3. Loosen the screws of the clamping strips so as to allow the
strips to
drop down slightly 3.
4. Remove the air separation plates:
-Unscrew bolts 4 and 5.
- Extract the plates.
5. Extract the plate heat exchangers:
- Via the side: 6.
- Via the underside: 7.
6. The last exchanger is located behind the by-pass valve.
Make room in order to extract the exchanger:
- Open the value of the by-pass 8.
- Unscrew the valve motors from the valve 9.
- When extracting via the underside:
Push the by-pass slightly to the side.
- When extracting via the side:
Disconnect the cables located on top of the by-p
ass
and
extract the by-pass via the underside of the unit.
- Extract the last exchanger.
7. Clean the plate heat exchangers by spraying water through
them.
8. Return all components to their places in reverse order.
Note:
n Tighten the screws/bolts of the air separation plates
and the clamping strips again, so that the exchangers
are clamped fast and no air leaks can arise.