Section 5: Maintenance
Maintenance
Section 5: Maintenance
NOTICE
Before carrying out any maintenance operation, it is necessary to close the pneumatic feed line
and exhaust the pressure from the actuator cylinder and from the control unit, to ensure safety
of maintenance staff.
!
WARNING
Installation, commissioning and maintenance and repair works should be carried out by
qualied staff.
5.1 Routine Maintenance
ALGAS actuators have been designed to work for long periods in the severest conditions
with no need for maintenance.
NOTICE
Periodicity and regularity of inspections is particularly inuenced by specic environmental
and working conditions. They can be initially determined experimentally and then be
improved according to actual maintenance conditions and needs.
Anyway every 2 years of operation the following is recommended:
1. Check that the actuator operates the valve correctly and with the required operating
times. If the actuator operation is very infrequent, carry out a few opening and
closing operations with all the existing controls (remote control, local control,
emergency controls, etc.), if this is allowed by the conditions of the plant.
2. Check that the signals to the remote control desk are correct.
3. Check that the air supply pressure value is within the required range.
4. If there is an air lter on the actuator, bleed the condense water accumulated in the
cup by opening the drain cock. Disassemble the cup periodically and wash it with
soap and water; disassemble the lter: if this is made up of a sintered cartridge, wash
it with nitrate solvent and blow through with air. If the lter is made of cellulose, it
must be replaced when clogged.
5. Check that the external components of the actuator are in good conditions.
6. Check all the paint-coat of the actuator. If some areas
are damaged, repair the paint-
coat according to the applicable specication.
7. Check that there are no leaks in the pneumatic connections. If necessary tighten the
nuts of the pipe ttings.