EasyManua.ls Logo

Binder M Series - Selecting between Set-Point Ramp and Set-Point Step; Program Entry as Set-Point Ramp or as Set-Point Step

Default Icon
71 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M (E2) 04/2019 page 29/71
9.2 Selecting between set-point ramp and set-point step
Temperature set-points always refer to the start of a program section, i.e., at the beginning of each pro-
gram section the entered temperature set-point is targeted. During program section operation, the tem-
perature gradually passes to the set-point entered for the next program section.
By appropriate planning of the program section timing, you can enter all kinds of temperature transitions.
Gradual temperature changes set-point ramp
The set-point changes its value gradually while proceeding from one program section to the next one
during the programmed section length. The actual temperature value (X) follows the continually mov-
ing set-point (W) at any time.
Program sections with constant temperature
The initial values of two subsequent program sections are identical; so the temperature remains con-
stant during the whole time of the first program section.
Sudden temperature changes set-point step
Steps are temperature changes (ramps) that occur during a very short interval. A section with a differ-
ent set-point follows two program sections with an identical set-point. If the duration of this transitional
program section is very short (minimum entry 1 sec), the temperature change will proceed rapidly
within the minimum amount of time.
01
02
03
04
05
06
07
08
09
W
t
Figure 7: Possible temperature transitions
The following chapter offers examples of programming a set-point ramp and a set-point step.
9.3 Program entry as set-point ramp or as set-point step
In order to avoid incorrect programming, we recommend plotting the temperature profile (chart template
in chap. 9.9) and entering the values into a table (templates in chap. 9.10).
The controller provides 8 operation lines that can be activated or de-activated for each program section.
Operating contact 1 is used to control the air flap position (ON = Air flap open, OFF = Air flap closed). The
other operation lines are non-functional.
The chamber does not provide active refrigeration, but you can program defined cooling down ramps
within the range of possible cooling-down times , e.g. in order to avoid tension in the material.

Table of Contents

Related product manuals