BOGE – RATIO compressor control for screw compressors
Control Parameterization1.5
Parameter overview
The control is already set for a bus coupler (BOGE-Bus-Address 32) for each
compressor according to customer specifications – as e.g. for Profibus. If
used another communication of RS485 then the following action is necesarry:
1. Enter Code 830 as described under parameterization → the display shows
one of the following fig. c or d.
2. Press ↑ or ↓-key to select the picture (bobus = BOGE-Bus, rtu = Modbus
type RTU) and quit by ↵-key. Depending upon selection one of the two
following fig. appears e or f:
With the BOGE-Bus only the desired address (flashing here 32) is to be
selected and quit by ↵-key, while with the Modbus-RTU after confirmation
of the address (flashing here on 0 = offline) by the key ↵, if address >0,
still additionally the Baud rate and the data format are adjustable as fol-
lows fig. g:
first the number 96 (= 9600 Baud) flashes – after confirmation by the ↵-
key 8E1 flashes (8E1 = 8 data bits, parity check of Even and 1 stop bit).
By means of key ↑ or ↓ then the necessary combination can be selected
(n = not parity check, o = odd).
3. Press ↵-key to overwrite the non-volatile EEPROM with the blinking value,
and the main display reappears.
A blinking Online symbol refers to a fault in the RS485 connection.
Code Function Page
019 Idling control for extremely short operation times 1.18
056 Anti freeze operation (only in mode
ready for operation
) 1.19
111 Set the compressor servicing interval and restart 1.13
134 Network independent ON-OFF memory (Auto-Restart) 1.18
210 External output enable 1.15
222 Set the motor servicing interval and restart 1.14
333
Set load cycles dependent servicing /inspection
1.14
and restart
360 Change target pressure values (P
max
and P
min
) 1.14
451 Remote On-Off control 1.17
733 Set continuous mode 1.19
770 Switching
Local-Remote
via key switch 1.16
830 Set RS 485-Bus-Address 1.20