EasyManua.ls Logo

Borri E2001 COMPACT - Figure 2 - Synoptic Panel

Borri E2001 COMPACT
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Front panel AC-UPS GD 128x64
8 OMX76014 Rev. A
3.2 LED FUNCTIONS SYNOPTIC DISPLAY
Figure 2 – Synoptic panel
LED 1
GREEN
Alternate input mains in tolerance range
RED
Alternate input mains fault
LED 2
GREEN
Rectifier OK
RED
Rectifier not OK
LED 3
GREEN
Battery ok
ORANGE
Test battery or battery flat
RED
Battery disconnected or test unsuccessful
LED 4
GREEN
Inverter OK
RED
Inverter not OK
LED 5
GREEN
Inverter static switch closed
OFF
Inverter static switch open
LED 6
GREEN
Output voltage OK
RED
Output voltage out of tolerance range
LED 7
OFF
Bypass static switch open
ORANGE
Bypass static switch closed
LED 8
GREEN
Alternate bypass mains in tolerance range
OFF
Alternate bypass mains fault
LED 9
OFF
Manual bypass disabled
RED
Manual bypass enabled
LED 10
GREEN
Buffer float charge
ORANGE
Rapid recharge (Boost)
RED
Manual or DC voltage not available from the rectifier
or the battery