Front panel AC-UPS GD 128x64
OMX76014 Rev. A
13
4.2.1 Reset UPS command
Figure 8
Commands Menu - Reset UPS
The UPS is equipped with internal guards that block the system in the event of
particular alarms. Using the arrows, you can change selection between the button and
with the V tick and the button with the X. When the button with the V tick is selected
confirming with the ENTER key you can release the alarm and reset normal operation.
In the event of persistent anomalies, the RESET command has no effect.
RESET is however necessary to reset normal conditions due to blocking conditions,
such as:
Maximum rectifier direct voltage output (alarm A5).
Alarm circuit error (Alarm A31).
Inverter switch off for maximum DC voltage.
The RESET command also has the function of acknowledging certain alarms or
events. The operator must press the RESET command to confirm the following alarms:
Safety timer for rapid recharge or manual charge (alarm A10).
Rapid recharge (and timed rapid recharge) remain disabled up to when A10 is
reset.
Battery test unsuccessful (alarm A23).
The battery test remains disabled until A23 is reset.
Manual charge shut-off (alarm A21).
In this case, RESET is sufficient to confirm the alarm without blocking any
function.