Front panel AC-UPS GD 128x64
30 OMX76014 Rev. A
Alarm
A12
RICB OPEN
Description
The input switch is open.
Possible
causes
Input switch is open.
Switch auxiliary contact faulty.
Solutions
1. Check the switch auxiliary contact is working.
2. If the alarm persists, contact our technical support service.
Alarm
A13
BCB OPEN
Description
The battery switch is open.
Possible
causes
Battery switch open.
Switch auxiliary contact faulty.
Solutions
1. Check the switch auxiliary contact is working.
2. If the alarm persists, contact our technical support service.
Alarm
A14
ROCB OPEN
Description
The rectifier output switch is open.
Possible
causes
Output switch open.
Switch auxiliary contact faulty.
Solutions
1. Check the switch auxiliary contact is working.
2. If the alarm persists, contact our technical support service.
Alarm
A15
FLAT BATTERY
Description
Battery is flat.
Possible
causes
Battery flat due to mains fault.
Rectifier fault.
Solutions
1. Check which alarms are present and execute the indicated
procedures.
2. If the alarm persists, contact our technical support service.
Alarm
A16
MIN BATTERY LEVEL 1
Description
The battery reaches the first minimum level.
Possible
causes
Level 1 flat battery due to mains fault.
Rectifier fault.
Solutions
1. Check the actual value of the battery voltage.
2. Check which alarms are present and execute the indicated
procedures.
3. If the alarm persists, contact our technical support service.