Front panel AC-UPS GD 128x64
36 OMX76014 Rev. A
Inverter output short circuit
Possible
Inverter output short circuit
Solutions
1. Eliminate the causes of the short circuit in inverter output
2. If the alarm persists, contact our technical support service.
Description The thermal image is activated in the event of prolonged overload.
Once the thermal image has intervened, the inverter stops for 30
minutes and then re-starts.
Possible
causes
Output overload
Measurement circuit fault
Solutions
1. Check the loads connected to the output to the inverter and, if
necessary, reduce the load
2. If the alarm persists, contact our technical support service.
Description Bypass not available or voltage or frequency of bypass out of
Possible
causes
Voltage out of limit permitted
Frequency out of limit permitted
Bypass cyclic direction incorrect
Solutions
1. Check the bypass voltage parameters are within the range
permitted
2. If the alarm persists, contact our technical support service.
The bypass feeds the load
Possible
causes
Transfer on bypass from bypass switch
Inverter fault or switched off
Solutions
1. If the inverter is off, switch it on
2. If the alarm persists, contact our technical support service.