Start-up, shut-down & manual bypass
8 OMX76015 REV. A
14
BYPASS STARTUP
CLOSE SBCB
Close SBCB
(if present)
15
BYPASS STARTUP
PLEASE WAIT
The micro-processor controls all the
bypass parameters (voltage, phases
succession, frequency) are within the
tolerance limits. The green indicator light
of LED #9 is on. The bypass static is
closed and the orange indicator light of
LED #8 switches on.
16
OUTPUT STARTUP
CLOSE OCB
Close OCB
The green indicator light of LED #7 is
on.
17
OUTPUT STARTUP
OPEN MBCB
Open MBCB.
The orange indicator light of LED #10
switches off.
18
INVERTER STARTUP
MOVE SELECTOR ON
Move selector
(if present)
If the inverter ON/OFF selector is
present and in the OFF position, the
display asks for its movement to the ON
position.
19
INVERTER STARTUP
PLEASE WAIT
The inverter IGBT bridge starts to
modulate and the output voltage of the
inverter reaches the nominal value. The
green indicator light of LED #5 is on.
20
INVERTER STARTUP
MOVE BYPASS SWITCH
Move the
NORMAL-
BYPASS
switch to
the NORMAL
position
The inverter has started. The load is
powered by the inverter. The green
indicator light of LED #6 switches on
and LED #8 switches off.
21
DEVICE STARTUP
PLEASE WAIT
The micro-processor controls all the
output parameters (voltage, phases
succession, frequency) are within the
tolerance limits.
22
UPS MODEL/DIMENSIONS
OUTPUT VOLTAGE/CURRENT