180 en | Points Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
Notice!
If the configuration option, Wireless Module Type, page 252, is set to B810 RADION Wireless,
the control panel is limited to 1512 wireless devices (1000 keyfobs, 504 points, and 8
repeaters). Wirelessis only a valid option if the number of points with Point Sourceset to
Wirelessdoes not exceed 504, plus the number of users assigned a valid keyfob RFID does
not exceed 1000, and the number of repeaters does not exceed 8. Note, Point Sourceis used
instead of RFID as the installer might have assigned several points to wireless without adding
any RFIDs.
NOTE: To expand or collapse the list of Point numbers, use the arrows at the top of the RPS
screen.
RPS Menu Location
Points > Point Assignments > RADION RFID (B810)
10.1.10 RADION Device Type
Default: Blank
Selections:
– Glass Break
– Smoke
– Inertia
– Door Window Contact
– Recessed Door Window
– Motion Dual
– Motion PIR
– Ceiling Mt.Motion
– Universal TX
– Bill Trap
– Curtain Motion
– CO Detector
– Panic, One Button
– Panic, Two Button
This parameter allows point source options to be set to wireless.
If the wireless module type is set to B810 Wireless Device, there is no limit on how many Point
Sourceoptions can be set to wireless. (Note: Even with keyfob supervision enabled, the
wireless device should support 1800 devices.)
Each wireless device contains corresponding input functions. Enable or disable input
functions by clicking the corresponding checkbox in the dialog box.
Device type Input 1 Input 2 Input 3 Input 4
Glass break Glass break
alarm
Not used Not used Not used
Smoke Smoke alarm Not used Not used Not used
Inertia Reed alarm Loop input Vibration alarm Not used
Door window
contact
Reed alarm Not used Not used Not used
Recessed door
window
Reed alarm Not used Not used Not used