98 en | Area Wide Parameters Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
Shared Area Characteristic Description
Force Arming a Shared Area When [CHECK AREA] is displayed, press the
NEXT key until the Force Arm? prompt is
shown.. Pressing the ENTER key will force
arm the Shared area if: the user has authority
to bypass points, the point is bypassable,
AND the number of faulted points does not
exceed the force arm max amount for the
Shared area. Remember to include the
Shared area in the Associate area's scope.
Viewing Shared Area Armed Status [VIEW AREA STATUS] can be used from a
keypad outside of the Shared area to view
the Shared areas armed state.
Silencing Sounders in the Shared Area Shared area alarms and troubles can be
silenced from any keypad.
To silence sounders, the user must have an
authority level assigned to the Shared area.
Access Control Readers Assigned to the
Shared Area
If the entry area is armed and is a Shared
area, then the exit delay will restart and allow
a user to walk to an Associate area and
disarm. If the card reader assigned to the
Shared area includes any Associate area in
the D## KP# Scope (in the ACCESS
CONTROL section, both the Associate area
and Shared area will disarm when the card is
presented.
Closing Reports for Shared Areas If closing reports for Shared areas are
required, Passcodes must also have a valid
authority level assigned in the Shared area.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Area Type
4.1.13 Two Man Rule?
Default:No
Selections:
– Yes - two valid and unique passcodes, entered using the same keypad, are required to
disarm the area.
– No - one passcode with a valid authority level can disarm the area.
This parameter sets the requirement for two valid passcodes to be entered on the same
keypad to disarm the area.
Notice!
To comply with SIA CP-01 False Alarm Reduction, set this parameter to No for all enabled
areas. Refer to SIA CP-01 Verification for more information.
Use this parameter in an area that is disarmed from All On using a keypad with Scope, page
111. An alarm event occurs if entry delay ends before the second valid passcode is entered.

Table of Contents

Other manuals for Bosch B8512G

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch B8512G and is the answer not in the manual?

Bosch B8512G Specifications

General IconGeneral
ModelB8512G
CategoryControl Panel
Power Supply12 VDC
SeriesG Series
Areas8
PGM Outputs on Board8
On-board EthernetYes
Wireless SupportYes
ManufacturerBosch
Input Voltage16.5 VAC
Users500
Communication FormatsIP, GSM, PSTN
CompatibilityCompatible with Bosch detectors, keypads, and communication modules