Fan Motor Options
14.3.2 Constant Airflow Motors Performance Data—Horizontal Configuration
Table 15 Constant Airflow Motors Performance Data—Vertical Configuration
Model Fan Speed
Default
Factory
Motor
Setting
CFM
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
CL015
A—Low 440 440 440 440 440 440 440 440 430 420 — —
A—Normal X 500 500 500 500 500 500 500 500 490 480 — —
A—High 590 590 590 590 590 590 590 590 590 575 — —
CL018
D—Low 500 500 500 500 500 500 500 500 500 500 — —
D—Normal X 580 600 600 600 600 600 600 600 590 580 — —
D—High 660 680 700 700 700 700 700 680 650 620 — —
CL024
B— Low 620 650 650 650 650 650 650 640 630 600 — —
B—Normal X 750 780 800 800 800 800 800 780 700 650 — —
B—High 880 900 900 900 900 900 900 880 800 700 — —
CL030
A—Low 780 800 800 800 800 800 800 800 700 650 — —
A—Normal X 920 950 950 950 950 950 950 900 750 700 — —
A—High 1050 1050 1050 1050 1050 1050 1050 1000 950 900 — —
CL036
A—Low 960 980 1000 1000 1000 1000 1000 1000 1000 1000 1000 —
A—Normal X 1150 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 —
A—High 1310 1340 1340 1340 1340 1340 1340 1340 1340 1340 1340 —
CL042
B—Low 1120 1160 1160 1160 1160 1160 1160 1160 1160 1160 1160 —
B—Normal X 1340 1350 1400 1400 1400 1400 1400 1400 1400 1400 1380 —
B—High 1530 1550 1550 1550 1550 1550 1550 1550 1550 1530 1480 —
CL048
A—Low 1350 1350 1350 1350 1350 1350 1350 1350 1350 1350 — —
A—Normal X 1560 1600 1600 1600 1600 1600 1600 1600 1600 1600 — —
A—High 1790 1820 1820 1820 1820 1820 1820 1820 1820 1760 — —
CL060
A—Low 1620 1620 1620 1620 1620 1620 1620 1620 1620 1620 1610 1600
A—Normal X 1900 1940 2000 2000 2000 2000 2000 2000 2000 1970 1900 1900
A—High 2150 2150 2150 2150 2150 2150 2150 2150 2100 2050 2000 1950
CL070
A—Low 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800
A—Normal X 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100 2100
A—High 2380 2400 2400 2400 2400 2400 2400 2400 2300 2250 2200 2150
Air flow is 70% of tabulated values during fan-only operation. Air flow is 80% of tabulated value during passive-dehumidification mode
when enabled.
| 49