6 720 821 651 (2017/05) CRC200
14 | Switching off power
5.2 Checklist: Important settings for
commissioning
Always perform commissioning so that the system operates as
needed. Based on experience, the following settings are very
important to satisfy the system user:
• Control type: outdoor reset ( ) with or without the
influence of the room temperature, or room temperature-
dependent
• Heating curve ( ): Adapted with reference to the
design temperature, minimum outdoor temperature and
other settings
• DHW priority: A heat demand for hot water has priority or
hot water and heating have the same priority (if possible
hydraulically)
• Time program: Determines when heating is active, see
user manual for details.
How to change settings in the service menu is described in
Chapter 8. Alternatively see the user manuals.
6 Switching off power
The user interface is powered via the BUS system and is always
on. The system is switched off only for maintenance work,
for example.
▶ Disconnect power from the entire system and all BUS
users.
Available only when outdoor sensor is connected and Frost protect is set to by Outdoor Temp
or Room - Outside.
Frost thresh. appears on the display. You can set the threshold outdoor temperatur for frost
protection. For further details see table 9.
▶ Press the dial.
▶ Turn the dial to change the temperature.
▶ Press the dial to switch to the next setting.
Heating Start appears on the display.
▶ Press the dial.
▶ Turn the dial to select YES and press the dial.
Configuration has been completed. The installation date of the CRC200 is set
automatically.
-or-
▶ Turn the dial to select NO and press the dial.
The system configuration continues.
Upon selecting YES the CRC200 is configured as a controller. The heating system and possibly water heating are operating.
Following configuration, only the menu items relevant for the configured system are displayed.
Basic settings
Table 4 Basic settings
6 720 811 156-36.1O
Frost thresh.
The installation date of the CRC200 is set
automatically when the configuration is
confirmed initially by starting the heating
system.
After a prolonged power failure or extended
period of idleness, the date and time may need
to be reset. All other settings are retained
permanently.