Menu item Possible values Description
Outdoor Temp.
()
– 40...122 °F
( – 40...50 °C)
The currently measured outdoor temperature is available only if an outdoor
temperature sensor is installed.
Appl. oper. ON Burner operating
OFF Burner not operating
Appl.set sply 68...194 °F (20...90 °C) Supply temperature required at the heat source (set temperature)
Appl.act.sply 68...194 °F (20...90 °C) Supply temperature measured at the heat source (actual temperature)
Appl.max.sply 95...194 °F (35...90 °C) Maximum supply temperature set at the heat source
LLH Temp. 68...194 °F (20...90 °C) Current hot water temperature in the low-loss header
HC Operation OFF Current operating mode of assigned heating zone, User interface operating
instructions
Heating
Setback
Summer
Manual
HC set.sply 68...194 °F (20...90 °C) Required supply temperature in assigned heating zone
HC act. sply. 68...194 °F (20...90 °C) Measured supply temperature in heating system
Set Room Temp OFF Heating switched off, e. g. in the summer
41...86 °F (5.0...30.0 °C) Desired room temperature
Room Temp. 41...86 °F (5.0...30.0 °C) Measured room temperature
DHW Operation ON Water heating active
OFF Water heating not active
Set DHW Temp 59...176 °F (15...80 °C) Desired hot water temperature
DHW Temp. 59...176 °F (15...80 °C) Measured hot water temperature
Table 10 Info menu