D6412/D4412 Operation and Installation Guide
Page 60 © 2003 Bosch Security Systems45349E
D6412/D4412
Installation Label
Aux
Pwr
+
Aux Pwr -
Bosch Security Systems recommends
testing the entire system at least once
a week, and having a qualified
technician check the system at a
minimum of once every 3 years.
This equipment has been type tested and found to comply with the specifications in Part 15 of FCC rules for Class B
Computing Devices. Operation is subject to the two following conditions (1) this device may not cause any interference,
and (2) this device must accept any interference received including interference that may cause undesired operation.
Complies with Part 68, FCC Rules.
FCC Registration Number:
ESVMUL-46531-AL-E
0.1B
This system should be installed in accordance with the National Electrical Code, NFPA 70, the National Fire Alarm
Code, NFPA 72 and the local authority having jurisdiction. Depending on the application, the installation is to be in
accordance with one or more of the following UL standards: UL681 Installation and Classification of Mercantile and
Bank Burglar Alarm Systems; UL1076 Proprietary Burglar Alarm Systems and Units; UL1641 Installation and
Classification of Residential Burglar Alarm Systems. Printed information describing proper installation, operation,
testing, maintenance, repair service and response to an alarm is to be provided with this equipment.
Warning
: Owner's Instruction Notice: Not to be removed by anyone except occupant.
Suitable for the following applications: 1) Household Burglar Alarm System Units, Grade A. 2) Household Fire Warning System Units. 3) Police Station
connect, Grade A Mercantile Premise alarm system, Grade A Mercantile Safe and Vault alarm system and Grade AA Mercantile Safe and Vault alarm system
when installed in conjunction with Model D8122 derived channel subscriber terminal unit. For all Police Station applications and grades, Model D8108A Attack
Resistant Enclosure with a UL Listed local sounding device is required. 4) Local, Grade A Mercantile Premise alarm system and Grade A Mercantile Safe and
Vault alarm system. For all local applications and grades, Model D8108A Attack Resistant Enclosure and a UL Listed local sounding device is required.
5) Central Station, Grade C application. Central Station, Grade B when installed with a UL Listed local sounding device. Central Station, Grade AA when installed
with Model D8122 derived channel subscriber terminal unit. 6) Proprietary Burglar Alarm units, Grade A. Proprietary Burglar Alarm unit, Grade BB when installed
with the Model D8122 derived channel subscriber terminal unit. D4412 must be installed in accordance with D6412/D4412 Installation Instructions (P/N:45349).
P/N:50487D 10/02
© 2002 Bosch Security Systems
D4412
400 mA for Fire and
Combined Fire/
Burglary;
1500 mA for UL
Burglary;
1850 mA for other*
Applies to all four outputs combined.
Use compatible
NAC such as
Bosch Security
Systems D440
Powered Sensor Loop
suitable for Two-Wire
Smoke Detectors 2.2 k
Ω
Resistor required at End of
Line. For compatible smoke
detectors, see D6412/D4412
Technogram (P/N:46928).
The UL Panel
Compatibility Identifier = B.
Also available for Four-
Wire Smoke Detectors such as Bosch Security Systems
D273TH.
Note 1
: A supervisory alarm output module must be used
on these terminals for household fire applications
Note 2
: Jumper J2-PO1 must be in place for connection
to NAC or other powered alarm device.
WARNING
: THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE FOR L-1(LOOP 1)
THAT RESULTS IN A DELAY OF THE SYSTEM ALARM SIGNAL WHEN PROGRAMMED
FOR THIS FEATURE. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING DEVICES SHALL BE
CONNECTED TO L-1 WHEN PROGRAMMED FOR ALARM VERIFICATION, UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
This box will be checked if L-1 is
programmed for Alarm Verification.
Installer Switch
Disables Arming,
Reports, and Relays.
Lock for local
programming.
All external connections are inherently Class 2 power limited.
256
3
4
L-3 Com L-4 L-5 Com L-6 L-7 Com L-8PO3 PO2
Alrm
+
AB
+-
Com L-2PO4
PO1
L-1
Installer
Keypad
Connect
Lock
Installer
Switch to
program.
Earth Ground
Do not connect to a receptacle
controlled by a switch. Do not
share with
other
equipment.
D4412 uses a
CX4010 UL Listed
Class 2 Transformer
18 VAC 22 VA 60 HZ
Green
Yellow
Red
Black
ABCD
P
S
Keypads, Expanders
Printer modules &
Communication modules
(up to 19 total devices)
P
S
P
S
P
S
Data
Data
(a) The delay (power-up) (start-up) time marked on the
installation wiring diagram of the smoke detector or
on the installed smoke detector(s) is to be used.
System Delay Chart
Circuit
(Loop)
Control Unit
Delay - Sec
Smoke Detector
Model Delay - Sec
1 16 sec
(a)
R1
T1
R
T
Red
Brown
Green
Gray
R1
T1
R
T
Incoming
Phone
Line
Use Bosch
Security Systems
D164
Phone Cord
or equivalent.
Ground Start
requires
D133/D134.
78
Supervised Loops
Open 7.7 to 14.0 VDC
Normal 6.3 to 7.3 VDC
Short 0.0 to 6.0 VDC
2.2 k
Ω
Resistor
(P/N:47819)
Required at End of Line
1
+
-
see
Note 1
Auxilliary Powered Devices 11.5 to 12.4 VDC. Below 10.2 VDC, the D4412 stops processing Loop inputs.
With 7.0 Ah battery,
120 mA for 24 hrs for Fire and Combined Fire/Burglary,
400 mA for 4 hrs for UL Burglary.
600 mA for other*
Include keypads in calculations.
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 600 mA for the Control Panel
and All Accessory Devices. For System loading, See D6412/D4412 Installation Instructions
(P/N:45349). Requirements for battery standby time may reduce
allowable output.
CAUTION
: See D6412/D4412 Installation Instructions (P/N:45349) for power requirements relating
to terminals [Alrm+] and [+Aux].
PO1 Terminals can be configured
as an alarm power output. JP2-
PO1 Jumper must be closed.
Maximum charging
current is 1.1 A.
BATTERY
: Replace
every 3 to 5 years.
Use Bosch Security
Systems Model
D126, 12 V 7 Amp HR
Sealed Lead Acid
Battery for Burglary or
Combination Fire and
Burglary Systems. For
additional load or
standby power, refer
to battery calculation
sheet in D6412/D4412
Installation Instructions
(P/N:45349).
Outputs PO3 &
PO4 can sink up
to 500 mA 12
VDC. Use D133/
D134 for larger
loads.
See D6412/D4412 Installation Instructions
(P/N:45349) for System Wiring Diagram
Premises
Phone
JP2
Output PO2 can be used
with Alarm+ as a
supervised siren driver.
Connect an approved
4 or 8
Ω
siren.
Alternatively, PO2 can
sink up to 500 mA 12
VDC. Use D133/D134
for larger loads.
P/N
25899
* Not investigated by UL.
Supervised with 2.2 k
Ω
EOL Resistor
(P/N: 47819).
Typical Initiating Devices
are Door Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.
Minimum system requirements for Classification in
Accordance with ANSI/SIA CP-01-2000:
UL Listed and Classified control unit Model D4412;
UL Listed and Classified keypad, one or more of
the following:
D621(W), D623(W), D625(W);
UL Listed Local Bell.