Subject to change without prior notice Revised 11-11
6720220327
Pressuredropinliquidmustnotexceed30psi
orerraticoperationandthermostaticexpan-
siondamagewilloccur.
All piping must be supported independent of coils
to prevent vibration and stress on coil headers.
Swing joints or exible ttings must be provided to
absorb expansion and contraction strains. Rig id
piping reduces the effectiveness of vibration
isolators. Water piping should always be connected
so that the entering water is on the bottom
connection of the water coil. Coils must be
adequately vented in order to prevent air binding.
Units are provided with manual air vents mounted
through the manifold panel.
Supply and return chilled water piping to the coil
should be ¾ inch ID up to 42,000 BTUs, 1 inch on
units greater than 42,000 BTUs. Water piping must
always be connected so that the entering water is
on the leaving side of the coil.
If a residential water heater is used for space
heating water, do not exceed a distance of 70 feet
between the air handler and the water heater. The
water heater should be the quick recovery type. Air
handler and water heater must be located indoors
and not subject to freezing temperatures.
Airhandlermustbelocatedsothatifany
connectionsshouldleak,waterwillnotcause
damagetotheadjacentarea.Whensuch
locationscan’tbeavoided,asuitabledrain
panshouldbeinstalledundertheairhandler,
notover1-1/2”deep,withminimumlengthand
widthatleast2”greaterthantheairhandler
dimensionsandconnectedtoanadequate
drain.Undernocircumstancesisthemanu-
facturertobeheldlibelforanywaterdamage
inconnectionwiththisairhandler.
Total piping should not exceed 140 feet. All piping
should be ¾" ID (7/8" OD) copper. CPVC piping
may be used in applications where the water
temperature does not exceed 150°F. It is
recommended that the water shut-off valve for the
water heater be located close to the water heater.
Isolation valves are also recommended.
It is recommended that any devices installed,
which could create a closed system, have a by-
pass and/or the system have an expansion tank to
relieve the pressure built up by thermal expansion
in the water system.
Toxicchemicalssuchasusedfortreatmentof
boilersornon-potablewaterheatingappli-
ancesshallneverbeintroducedintoapotable
waterspaceheatingsystem.
Whenthesystemrequiredwaterattempera-
tureshigherthanrequiredforotheruses,a
meanssuchasamixingvalveshallbe
installedtotemperthewaterforthoseusesin
ordertoreducethescaldhazardpotential.
After piping has been installed, allow the system
to ll with water and check connections for leaks.
To insure complete lling of the system, follow
start-up procedure.
Thermal expansion valve (TXV) can be used on
both heat pump and air conditioning applications.
All TXVs have a built in check valve making them
heat pump capable. All are externally equalized
with non-adjustable superheat and are available
with 15% bleed construction. Hard start capability
for outdoor units is not normally required when
15% bleed valve is used. The external equalizer
line attached to the TXV has a female are nut with
built in Schrader valve depressor that attaches to
the Schrader valve port provided on coils.
Withreferencetothegure9,theTXV
assemblyistobeinstalledbetweenthe
owratordistributorandtheexistingliquidline
attachedtotheowratordistributor.