54 | Operating Temperatures and pressures SM Series Heat Pump
SM Series Heat Pump6 720 220 406 (2013/1) Subject to change without prior notice
SM036
Part
Load
30°
4.5 73-89 266-325 5-6 15-18
9.0 77-94 272-333 3-4 16-19
40°
4.5 117-143 189-231 14-17 18-22 86-105 279-341 6-7 17-21
9.0 112-137 178-217 8-9 19-24 90-110 286-350 4-5 18-22
50°
4.5 126-154 221-270 14-17 18-21 105-125 293-358 7-8 20-24
9.0 121-148 207-253 8-9 19-23 109-130 300-366 5-6 21-25
60°
4.5 131-160 252-308 13-16 17-21 110-134 306-374 8-10 22-27
9.0 125-153 237-290 8-9 18-22 115-141 314-383 6-7 23-29
70°
4.5 135-165 284-347 13-16 17-20 122-150 320-391 9-11 24-30
9.0 130-158 266-326 7-9 18-22 129-157 327-400 6-8 26-32
80°
4.5 140-171 320-391 13-16 16-20 134-164 333-407 11-13 27-33
9.0 134-164 300-367 7-9 17-21 141-172 341-417 7-9 28-35
90°
4.5 144-176 360-440 13-16 16-19 147-179 347-424 12-14 29-36
9.0 138-169 338-414 7-9 17-21 154-188 355-434 8-10 31-38
100°
4.5 149-182 405-495 13-15 15-19
9.0 143-174 381-465 7-9 16-20
SM036
Full
Load
30°
4.5 74-90 244-299 3-4 13-15
9.0 78-95 251-306 2-3 13-16
40°
4.5 122-149 183-224 14-18 19-23 87-106 257-314 4-5 15-18
9.0 117-143 172-210 8-10 20-24 91-111 263-322 3-3 16-19
50°
4.5 131-160 214-261 14-18 18-22 95-105 269-329 5-6 17-20
9.0 126-154 201-245 8-10 19-24 100-125 276-337 3-4 18-22
60°
4.5 136-166 244-298 14-17 18-22 111-136 282-344 6-7 19-23
9.0 131-160 230-281 8-10 19-23 117-143 289-353 4-5 20-24
70°
4.5 141-172 275-336 14-17 17-21 124-152 294-360 7-8 21-25
9.0 135-165 258-316 8-10 18-22 131-160 302-369 5-6 22-27
80°
4.5 145-178 310-378 14-17 17-20 136-166 307-375 8-9 23-28
9.0 140-171 291-356 8-10 18-22 143-175 314-384 5-6 24-30
90°
4.5 150-183 349-426 14-17 16-20 149-182 319-390 8-10 25-30
9.0 144-176 328-401 8-9 17-21 156-191 327-400 6-7 26-32
100°
4.5 155-189 392-480 13-16 16-19
9.0 149-182 369-451 8-9 17-21
Operating temperatures and pressures
COOLING HEATING
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as
a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º
w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid
temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development,
specifications are subject to change without notice.

Table of Contents

Other manuals for Bosch Greensource CDi Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Greensource CDi Series and is the answer not in the manual?

Bosch Greensource CDi Series Specifications

General IconGeneral
BrandBosch
ModelGreensource CDi Series
CategoryHeat Pump
LanguageEnglish

Related product manuals