Operating Temperatures and pressures | 55SM Series Heat Pump
6 720 220 406 (2013/1)SM Series Heat Pump
SM048
Part
Load
30°
6.0 64-78 248-303 5-6 15-18
12.0 67-82 254-311 3-4 16-19
40°
6.0 109-134 183-224 18-22 19-23 75-91 261-319 6-8 17-21
12.0 105-128 172-210 10-12 20-25 79-96 267-327 4-5 18-23
50°
6.0 118-144 214-261 18-22 19-23 78-90 273-334 8-10 20-24
12.0 113-138 201-245 10-12 20-24 82-95 280-342 5-7 21-26
60°
6.0 122-149 244-298 17-21 18-22 96-117 286-349 9-11 22-27
12.0 117-143 230-281 10-12 19-24 101-123 293-358 6-8 24-29
70°
6.0 126-154 275-336 17-21 18-22 107-131 299-365 11-13 25-30
12.0 121-148 258-316 10-12 19-23 113-138 306-374 7-9 26-32
80°
6.0 130-159 310-378 17-21 17-21 117-143 311-380 12-15 27-33
12.0 132-153 291-356 10-12 18-22 123-151 319-390 8-10 29-35
90°
6.0 134-164 349-426 17-20 17-20 128-157 324-396 13-16 29-36
12.0 129-158 328-401 9-12 18-22 135-165 332-406 9-11 31-38
100°
6.0 139-170 392-480 16-20 16-20
12.0 133-163 369-451 9-11 17-21
SM048
Full
Load
30°
6.0 71-87 277-339 6-7 15-19
12.0 75-92 284-347 4-5 16-20
40°
6.0 118-144 194-237 21-25 19-23 84-102 291-356 7-9 18-22
12.0 113-138 182-223 12-14 20-24 88-108 299-365 5-6 19-23
50°
6.0 127-155 226-276 21-25 18-22 92-110 305-373 9-11 20-25
12.0 122-149 213-260 12-14 19-24 98-120 313-383 6-7 21-26
60°
6.0 131-160 259-316 21-25 18-22 108-132 320-391 10-13 23-28
12.0 126-154 243-297 12-14 19-23 113-138 328-400 7-9 24-29
70°
6.0 136-166 291-355 20-25 17-21 120-147 334-408 12-15 25-31
12.0 130-159 273-334 12-14 18-22 126-154 342-418 8-10 27-32
80°
6.0 140-171 328-401 20-24 17-20 131-161 348-425 14-17 27-34
12.0 135-165 308-377 11-14 18-22 138-169 356-436 9-11 29-36
90°
6.0 145-177 369-451 20-24 16-20 144-176 362-442 15-18 30-37
12.0 139-170 347-424 11-14 17-21 151-185 371-453 10-12 32-39
100°
6.0 149-183 415-508 19-24 16-19
12.0 143-175 391-477 11-14 17-21
Operating temperatures and pressures
COOLING HEATING
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as
a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º
w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid
temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development,
specifications are subject to change without notice.

Table of Contents

Other manuals for Bosch Greensource CDi Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Greensource CDi Series and is the answer not in the manual?

Bosch Greensource CDi Series Specifications

General IconGeneral
BrandBosch
ModelGreensource CDi Series
CategoryHeat Pump
LanguageEnglish

Related product manuals